DC Field | Value | Language |
---|---|---|
dc.contributor.author | Choi, Jung-Chan | ko |
dc.contributor.author | Lee, Seung-Rae | ko |
dc.contributor.author | Lee, Dae-Soo | ko |
dc.date.accessioned | 2013-03-09T19:33:30Z | - |
dc.date.available | 2013-03-09T19:33:30Z | - |
dc.date.created | 2012-02-06 | - |
dc.date.created | 2012-02-06 | - |
dc.date.issued | 2011-12 | - |
dc.identifier.citation | COMPUTERS AND GEOTECHNICS, v.38, no.8, pp.949 - 958 | - |
dc.identifier.issn | 0266-352X | - |
dc.identifier.uri | http://hdl.handle.net/10203/97304 | - |
dc.description.abstract | The effect of varying the thermal properties of inhomogeneous unsaturated soil on the intermittent operation of a vertical ground heat exchanger (GHE) was simulated by a conjugate heat transfer simulation using a transient conductive heat transfer model. A three-phase soil model was used to introduce soil properties that vary with depth. The performance during the first few hours was significantly different from that of an analytical infinite line source model that assumes steady-state borehole conditions, although relatively good agreement was obtained thereafter. Unsaturated soil conditions afforded a 40% lower mean heat exchange rate than saturated conditions. This demonstrates the importance of considering unsaturated conditions in the design and performance evaluation of GHEs. (C) 2011 Elsevier Ltd. All rights reserved. | - |
dc.language | English | - |
dc.publisher | ELSEVIER SCI LTD | - |
dc.subject | THERMAL PERFORMANCE | - |
dc.subject | SYSTEMS | - |
dc.subject | MODEL | - |
dc.subject | PUMP | - |
dc.subject | PILE | - |
dc.title | Numerical simulation of vertical ground heat exchangers: Intermittent operation in unsaturated soil conditions | - |
dc.type | Article | - |
dc.identifier.wosid | 000296114200003 | - |
dc.identifier.scopusid | 2-s2.0-80052923259 | - |
dc.type.rims | ART | - |
dc.citation.volume | 38 | - |
dc.citation.issue | 8 | - |
dc.citation.beginningpage | 949 | - |
dc.citation.endingpage | 958 | - |
dc.citation.publicationname | COMPUTERS AND GEOTECHNICS | - |
dc.identifier.doi | 10.1016/j.compgeo.2011.07.004 | - |
dc.contributor.localauthor | Lee, Seung-Rae | - |
dc.contributor.nonIdAuthor | Lee, Dae-Soo | - |
dc.type.journalArticle | Article | - |
dc.subject.keywordAuthor | Ground source heat pump | - |
dc.subject.keywordAuthor | Ground heat exchanger | - |
dc.subject.keywordAuthor | Numerical simulation | - |
dc.subject.keywordAuthor | Unsaturated soil | - |
dc.subject.keywordAuthor | Intermittent operation | - |
dc.subject.keywordPlus | THERMAL PERFORMANCE | - |
dc.subject.keywordPlus | SYSTEMS | - |
dc.subject.keywordPlus | MODEL | - |
dc.subject.keywordPlus | PUMP | - |
dc.subject.keywordPlus | PILE | - |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.