Determination of design accidental fire load for offshore installations based on quantitative risk assessment with treatment of parametric uncertainty

Cited 3 time in webofscience Cited 0 time in scopus
  • Hit : 383
  • Download : 0
DC FieldValueLanguage
dc.contributor.authorChu, Bongsikko
dc.contributor.authorLee, Sangickko
dc.contributor.authorChang, Daejunko
dc.date.accessioned2017-03-28T06:54:05Z-
dc.date.available2017-03-28T06:54:05Z-
dc.date.created2016-12-26-
dc.date.created2016-12-26-
dc.date.issued2017-01-
dc.identifier.citationJOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, v.45, pp.160 - 172-
dc.identifier.issn0950-4230-
dc.identifier.urihttp://hdl.handle.net/10203/220928-
dc.description.abstractThis study investigated the critical issues for determining the design accidental load (DAL) fire procedure based on quantitative risk assessment (QRA) for offshore installations. Considerable attention was paid to parametric uncertainty in choosing the numerical values used for the frequency and consequence analysis. In particular, selecting the initial leak size was one of the most critical aspects, and inconsistent approaches for selecting this value resulted in different risks for identical systems. Frequency analysis of past investigations also overlooked the inaccuracy and unsuitability of statistical data. Accordingly, the estimated risks were significantly uncertain, and the lack of information about the results increased the risk of making the wrong decision. In this study, the Latin hypercube sampling (LHS) technique was used to treat parametric uncertainty in QRA. Different fire exceedance curves and DAL fires were demonstrated by selecting different sets of representative values. The distribution and confidence interval of the DAL fires showed a wide distribution with varying uncertain and critical parameters. Therefore, this procedure provided quantitative information on inherent uncertainty, and such additional information regarding DAL fires can lead to better decision making. (C) 2016 Elsevier Ltd. All rights reserved.-
dc.languageEnglish-
dc.publisherELSEVIER SCI LTD-
dc.subjectSYSTEMS-
dc.titleDetermination of design accidental fire load for offshore installations based on quantitative risk assessment with treatment of parametric uncertainty-
dc.typeArticle-
dc.identifier.wosid000393534000014-
dc.identifier.scopusid2-s2.0-85007179489-
dc.type.rimsART-
dc.citation.volume45-
dc.citation.beginningpage160-
dc.citation.endingpage172-
dc.citation.publicationnameJOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES-
dc.identifier.doi10.1016/j.jlp.2016.11.015-
dc.contributor.localauthorChang, Daejun-
dc.contributor.nonIdAuthorLee, Sangick-
dc.description.isOpenAccessN-
dc.type.journalArticleArticle-
dc.subject.keywordAuthorQuantitative risk assessment-
dc.subject.keywordAuthorDesign accidental load-
dc.subject.keywordAuthorFire exceedance plot-
dc.subject.keywordAuthorLatin hypercube sampling-
dc.subject.keywordAuthorParametric uncertainty-
dc.subject.keywordPlusSYSTEMS-
Appears in Collection
ME-Journal Papers(저널논문)
Files in This Item
There are no files associated with this item.
This item is cited by other documents in WoS
⊙ Detail Information in WoSⓡ Click to see webofscience_button
⊙ Cited 3 items in WoS Click to see citing articles in records_button

qr_code

  • mendeley

    citeulike


rss_1.0 rss_2.0 atom_1.0