In this paper, the results of nonlinear dynamic analyses of a concrete containment building under extreme loads are presented. The impact of a large commercial B747 airliner is investigated as the extreme load, and a rigid wall impact test is performed using commercial nonlinear finite element codes. The impact forces exerted by the aircraft are verified compared with the time-dependent impact force provided by OECD/NEA (2002), which was calculated based on the so-called Riera method. The rigid wall impact analysis shows that the finite element model of a B747 is appropriate for the purpose of the aircraft crash analysis exposed to the external hazard of