Inhibition of Pitting Corrosion Failure of Copper Tubes in Wet Sprinkler Systems스프링클러 구리배관의 공식 파손 억제

Cited 0 time in webofscience Cited 0 time in scopus
  • Hit : 556
  • Download : 0
The inhibition of pitting corrosion failure of copper sprinkler tubes in wet sprinkler systems was studied. First, an apparatus and technology for removing air in the sprinkler tubes by vacuum pumping and then filling the tubes with water were developed. Using this apparatus and technology, three methods for inhibiting the pitting corrosion of the copper sprinkler tubes installed in several apartment complexes were tested. The first one was filling the sprinkler tubes with water bubbled by high-pressure nitrogen gas to reduce the dissolved oxygen concentration to lower than 2 ppm. In the second method, the dissolved oxygen concentration of water was further reduced to lower than 0.01 ppm by sodium sulfite. In the third method, the sprinkler tubes were filled with benzotriazole (BTAH) dissolved in water. The third method was the most effective, reducing the failure frequency of the sprinkler tubes due to pitting corrosion by more than 80%. X-ray photoelectron spectroscopy analyses confirmed that a Cu-BTA layer was well coated on the inside surface of the corrosion pit, protecting it from corrosion. A potentiodynamic polarization test showed that BTAH should be very effective in reducing the corrosion rate of copper in the acidic environment of the corrosion pit.
Publisher
CORROSION SCIENCE SOC KOREA
Issue Date
2020-04
Language
Korean
Article Type
Article
Citation

CORROSION SCIENCE AND TECHNOLOGY-KOREA, v.19, no.2, pp.89 - 99

ISSN
1598-6462
DOI
10.14773/cst.2020.19.2.89
URI
http://hdl.handle.net/10203/274449
Appears in Collection
MS-Journal Papers(저널논문)
Files in This Item
There are no files associated with this item.

qr_code

  • mendeley

    citeulike


rss_1.0 rss_2.0 atom_1.0