습증기를 포함한 연소가스의 폐열 회수를 위한 열교환기 성능 예측

Cited 0 time in webofscience Cited 0 time in scopus
  • Hit : 461
  • Download : 3
A simulation program using the mass transfer correlation was constructed to analyze 1-D simplified condensing flow across the tube bank. Higher efficiency was anticipated by reducing the flue gas temperature down below the dew point where the water vapor in the flue gas is condensed at the surface of the heat exchanger; that is, the heat transfer by the latent heat is added to that by the sensible heat. Thus, there can be an optimum operating condition to maximize the heat recovery from the flue gas. The temperature rises of the flue gas and the cooling water between the inlet and the outlet of the tube bank were compared with the experimental data reported previously. The predicted results agree well with the experimental data. Using this simulation program, the parametric studies have been conducted fur various operating conditions, such as the velocities and temperatures of the vapor/gas mixture and the cooling water, the number of the rows, and the conductivity of the wall material.
Publisher
대한기계학회
Issue Date
2000
Language
KOR
Citation

대한기계학회 2000년 춘계학술발표대회 , v.1, no.2, pp.276 - 281

URI
http://hdl.handle.net/10203/15882
Appears in Collection
ME-Conference Papers(학술회의논문)

qr_code

  • mendeley

    citeulike


rss_1.0 rss_2.0 atom_1.0