공랭식 열교환핀이 부착된 열전모듈의 냉각 성능에 관한 연구Cooling Performance of Thermoelectric Module with Air-Cooled Heat Exchanger Fins

Cited 0 time in webofscience Cited 0 time in scopus
  • Hit : 622
  • Download : 0
Thermal performance of louver fin and plate fin in a thermoelectric cooling system with a duct-flow type fan arrangement is analytically evaluated. The thermoelectric cooling system consists of a thermoelectric module and two heat exchanger fins. The analytic results show that the optimized louver fin has lower thermal resistance than plate fin. The COP and heat absorbed rate of the thermoelectric cooling system with optimized louver fins are 10.3% and 5.8% higher than optimized plate fins, respectively.
Publisher
대한설비공학회
Issue Date
2010-03
Language
Korean
Citation

설비공학 논문집, v.22, no.3, pp.171 - 179

ISSN
1229-6422
URI
http://hdl.handle.net/10203/100831
Appears in Collection
ME-Journal Papers(저널논문)
Files in This Item
There are no files associated with this item.